Chapter 6. Maintaining the Library
84
Replacing the Air Filter
Spectra 10000 libraries have a front panel with a removable air filter. Inspect these
filters every three to four months and replace as necessary. If the filter is contaminated,
replace it. A clogged air filter may cause operational errors due to excessive
temperatures inside the library.
To order replacement filters, contact your sales representative.
Caution: Some environments may require more frequent filter inspection
and replacement. If library filters get clogged quickly, you
should consider moving the library to a more dust free location
or improve the environment where it is located.
If air filters have excessive clogging due to neglect, it is
recommended that the filter be replaced immediately. After
replacing the filter, all tape drive heads should be cleaned. The
inside of the library, including the tape cartridges, should also be
cleaned with a low-pressure vacuum.
To check and replace the filter:
1. Insert a plastic card into the front panel release on the left side of the faceplate’s
slotted grill (Figure 6-4).
Figure 6-4 The front panel release.